Appendix 1  Parameters      99 
EV2000 Series Universal Variable Speed Drive    User Manual 
Group 7: Terminal Function Parameters 
Para.  Name  LCD Display  Setting Range  Unit 
Factory 
setting
Modif
F7.10 
Bi-direction 
open 
collector 
output 
terminal Y1 
Y1 FUNC 
SELE 
0:Running signal(RUN) 
1:frequency arriving signal(FAR) 
2:frequency detection threshold (FDT1) 
3:frequency detection threshold (FDT2) 
4:overload signal(OL) 
5:low voltage signal(LU) 
6:external fault signal(EXT) 
7:frequency high limit(FHL) 
8:frequency low limit(FLL) 
9:zero-speed running 
10:Completion of simple PLC operation 
11:PLC cycle completion indication 
12:preset counting value arriving 
13:specified counting value arriving 
14:reference length arriving indication 
15:drive ready (RDY) 
16:drive fault 
17:extended functions of host 
18:Upper and lower limits of traverse operating frequency 
19: preset operating time out 
1 0 
× 
F7.11 
Bi-direction 
open 
collector 
output 
terminal Y2 
Y2 FUNC 
SELE 
1 1 
× 
F7.12 
Function 
selection of 
output relay 
RELAY 
OUTPUT 
1 16 
× 
F7.13  FAR duration  FAR RANGE  0.00~650.0Hz  0.01Hz  2.50Hz
○ 
F7.14  FDT1 level  FDT1 LEVEL  0.00~650.0Hz  0.01Hz  50.00Hz
○ 
F7.15  FDT1 lag  FDT1 LAG  0.00~650.0Hz  0.01Hz  1.00Hz
○ 
F7.16  FDT2 level  FDT2 LEVEL  0.00~650.0Hz  0.01Hz  25.00Hz
○ 
F7.17  FDT2 lag  FDT2 LAG  0.00~650.0Hz  0.01Hz  1.00Hz
○ 
F7.18
~ 
F7.25 
Reserved RESERVED -  - 0 * 
F7.26 
Functions of 
terminal AO1 
ANALOG 
OUTPUT1 
0: Output frequency before slip compensation (0~Max output frequency) 
1:Output frequency after slip compensation (0~Max output frequency) 
2:Preset frequency (0~Max output frequency) 
3:Output current (0~2 times of drive’s rated current) 
4:Output current (0~2 times of motor’s rated current) 
5:Output torque (0~2 times of motor’s rated torque) 
6:Output voltage (0~1.2 times of drive’s rated voltage) 
7:Bus voltage (0~800V) 
8:VCI (0~10V) 
9:CCI (0~10V/0~20mA) 
10:Output power (0~2 times of rated power) 
11:Extended function of host 2(0~65535) 
1 0 
○ 
F7.27 
Functions of 
terminal AO2 
ANALOG 
OUTPUT2 
1 3 
○ 
F7.28 
Functions of 
terminal DO(no 
output when 
F7.07=44~46) 
DIGITAL 
OUPUT 
1 0 
○ 
F7.29 
Analog output 
range 
ANALOG 
OUTPUT 
OFFSET 
Unit’s place of LED: AO1 offset selection 
0: 0~10V or 0~20Ma                1: 2~10V or 4~20mA 
Ten’s place of LED: AO2 offset selection 
0:0~10V or 0~20mA                1: 2~10V or 4~20mA  
1 00 
○ 
F7.30 
AO1 output 
gain 
A01 CALIB 
0.0~200.0% 0.1% 100.0%
○ 
F7.31 
AO2 output 
gain 
A02 CALIB 
0.0~200.0% 0.1% 100.0%
○ 
F7.32 
Maximum 
output 
frequency of 
DO 
MAX 
OUTPUT 
PULSE 
0.1~50.0 (up to 50k)  0.1  10.0k 
○ 
F7.33 
Preset counting 
value reaches 
reference value 
SET COUNT 
VALUE 
F7.34~9999 1 0 
○ 
F7.34 
Specified 
counting value 
SPECIFIED 
COUNT 
0~F7.33 1 0 
○