Emerson FB1100 Flow Computer Quick Start Guide
D301785X012
March 2019
12
Grounding
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
The flow computer includes a ground lug on the terminal plate.
1
Ground lug
Once you have installed the unit, run a ground wire between the ground lug and a
known good earth ground. You route the ground wire through one of the conduit
fittings.
Use stranded copper wire to earth ground and keep the length as short as possible.
Clamp or braze the ground wire to the ground bed conductor (typically a stranded
copper AWG 0000 cable installed vertically or horizontally).
Using a high-wattage soldering iron, tin the wire ends with solder before you insert
them into the chassis ground lug.
Run the ground wire so that any routing bend in the cable has a minimum radius of
30.48 cm (12 inches) below ground and 20.32 cm (8 inches) above ground.
For more information on grounding or if your installation uses cathodic protection, refer to
Site Considerations for Equipment Installation, Grounding, and Wiring (D301452X012).