EasyManuals Logo

Emerson Fisher FIELDVUE DVC6000 HW2 User Manual

Emerson Fisher FIELDVUE DVC6000 HW2
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
Instruction Manual
D103785X012
Maintenance and Troubleshooting
June 2017
70
5. Set the DIP switch on the PWB assembly according to table 6‐2. On units that have the optional 4-20 mA position
transmitter or switch hardware installed, set the Transmitter or Switch option according to table 6‐3.
Table 6‐2. DIP Switch Configuration
(1)
Switch Label Operational Mode DIP Switch Position
PT-PT 420 mA PointtoPoint Loop LEFT
Multi 24 VDC MultiDrop Loop RIGHT
1. Refer to figure 6‐5 for switch location.
Table 6‐3. Output Switch Configuration
(1)
Switch Label/Function DIP Switch Position
Transmitter LEFT
Switch RIGHT
1. Refer to figure 6‐5 for switch location.
X0432
Figure 6‐5. Printed Wiring Board (PWB) Connections and Settings
TRANSMITTER/SWITCH
SELECTION
TRAVEL SENSOR
CONNECTOR
TERMINAL BOX
CONNECTOR
OPERATIONAL
MODE SELECTION
TRAVEL SENSOR
CONNECTOR
TERMINAL BOX
CONNECTOR
OPERATIONAL
MODE SELECTION
X0463
Note
For the digital valve controller to operate with a 4 to 20 mA control signal, be sure the DIP switch is in the point‐to‐point loop
position.
6. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
7. Setup and calibrate the DVC6005 HW2 base unit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000 HW2 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000 HW2 Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000 HW2
CategoryController
LanguageEnglish

Related product manuals