Table 1-7. Hazardous Area Classifications—IECEx
Certificate Type Certification Obtained Entity Rating Temperature Code
Enclosure
Rating
IECEx
DVC60x0
DVC60x0S
(x = 1,2,3)
Intrinsically Safe
Gas
Ex ia IIC T5/T6 per drawing GE42990
Natural Gas Approved
Ui = 30 VDC
Ii = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
T5(Tamb 80C)
T6(Tamb 75C)
IP66
Single Seal Device
Flameproof
Gas
Ex d IIC T5/T6
Natural Gas Approved
T5(Tamb 80C)
T6(Tamb 75C)
IP66
Single Seal Device
Type n
Gas
Ex nC IIC T5/T6
Natural Gas Approved
T5(Tamb 80C)
T6(Tamb 75C)
IP66
Single Seal Device
DVC6005
Intrinsically Safe
Gas
Ex ia IIC T5/T6 per drawing GE42990
Natural Gas Approved
Ui = 30 VDC
Ii = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
Uo = 9.6 VDC
Io = 3.5 mA
Ca = 3.6 uF
La = 100 mH
Po = 8.4 mW
T5(Tamb 80C)
T6(Tamb 75C)
IP66
Single Seal Device
Flameproof
Gas
Ex d IIC T5/T6
Natural Gas Approved
T5(Tamb 80C)
T6(Tamb 75C)
IP66
Single Seal Device
Type n
Gas
Ex nC IIC T5/T6
Natural Gas Approved
T5(Tamb 80C)
T6(Tamb 75C)
IP66
Single Seal Device
DVC60x5
(x = 1,2,3)
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 per drawing GE42990
Ui = 30 VDC
Ii = 100 mA
Ci = 0 uF
Li = 0 mH
Pi = 160 mW
T4(Tamb 125C)
T5(Tamb 95C)
T6(Tamb 80C)
IP66
Flameproof
Gas
Ex d IIC T4/T5/T6
T4(Tamb 125C)
T5(Tamb 95C)
T6(Tamb 80C)
IP66
Type n
Gas
Ex nA IIC T4/T5/T6
T4(Tamb 125C)
T5(Tamb 95C)
T6(Tamb 80C)
IP66