Transducer Block
December 2009
4-49
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
PRESS_CAL
46
Supply Pressure Scale
SUPP_PRESS_SCALE
46.1 RW
MAN
OOS
> 0 CAL Data Type: Float
Supply Pressure Offset
SUPP_PRESS_OFFSET
46.2 RW
MAN
OOS
0 to 16383 CAL Data Type: Uint16
Pressure A Scale
PRESS_A_SCALE
46.3 RW
MAN
OOS
> 0 CAL Data Type: Float
Pressure A Offset
PRESS_A_OFFSET
46.4 RW
MAN
OOS
0 to 16383 CAL Data Type: Uint16
Pressure B Scale
PRESS_B_SCALE
46.5 RW
MAN
OOS
> 0 CAL Data Type: Float
Pressure B Offset
PRESS_B_OFFSET
46.6 RW
MAN
OOS
0 to 16383 CAL Data Type: Uint16
Pressure IP Bias
PRESS_IP_BIAS
46.7 RW
MAN
OOS
0100% 70% CAL Data Type: Float
Pressure MLFB Bias
PRESS_MLFB_BIAS
46.8 RW
MAN
OOS
0100% 50% CAL Data Type: Float
PRESS_TUNE
47
Pressure Cutoff Hi
PRESS_CUTOFF_HI
47.1 RW
MAN
OOS
25 125%,
> CUTOFF_LO
99.50% SETUP Data Type: Float
Pressure Cutoff Lo
PRESS_CUTOFF_LO
47.2 RW
MAN
OOS
25 125% <
CUTOFF_HI
0.50% SETUP Data Type: Float
Pressure Proportional Gain
PRESS_PROP_GAIN
47.3 RW
MAN
OOS
> = 0, < 32 2.2 SETUP
Data Type: Float
Proportional gain
Pressure Integral Gain
PRESS_INTEG_GAIN
47.4 RW
MAN
OOS
> = 0, < 32 0.1 SETUP
Data Type: Float
Integral resets per second
Pressure Rate Gain
PRESS_RATE_GAIN
47.5 RW
MAN
OOS
> = 0, < = 512 0 SETUP
Data Type: Float
Derivative gain
Pressure Integral Dead Zone
PRESS_INTEG_DEADZ
47.6 RW
MAN
OOS
= 0%, < = 2.0% 0.25% SETUP
Data Type: Float
Integrator Deadzone, 1/2 width
Pressure Integral Limit Hi
PRESS_INTEG_HI_LIM
47.7 RW
MAN
OOS
> = 0%, < = 100%,
>INTEG_LO
20% SETUP
Data Type: Float
Integrator limits
Pressure Integral Limit LO
PRESS_INTEG_LO_LIM
47.8 RW
MAN
OOS
< = 0%, > = 100%,
<INTEG_HI
20% SETUP
Data Type: Float
Integrator limits
Pressure Integral IC Hi
PRESS_INTEG_IC_HI
47.9 RW
MAN
OOS
>= 100%, < = 100% 12% Not used by the DVC6000f
Pressure Integral IC Lo
PRESS_INTEG_IC_LO
47.10 RW
MAN
OOS
>= 100%, < = 100% 12% Not used by the DVC6000f
Pressure MLFB Gain
PRESS_MLFB_GAIN
47.11 RW
MAN
OOS
> 0, < = 100 35 SETUP Data Type: Float
Temperature
TEMPERATURE
48 RO N/A N/A N/A
Data Type: Float
Electronics temperature Controls
AI channel 11
Target Travel
TRAVEL_TARGET
49 RO
Status
STATUS
49.1 RO
MAN
OOS
N/A
Data Type: DS-65
In Travel Control: Setpoint for valve
travel in %, post characterization.
In Pressure Control:
Setpoint for
implied valve travel as a % or
pressure range, post
characterization.
Value
VALUE
49.2 RO
MAN
OOS
N/A
Input Characterization
INPUT_CHAR
50 RW
MAN
OOS
1=Linear
2=Equal %
3=Quick Opening
4=Reserved
5=Custom
1=Linear SETUP Data Type: Enum (Uint8)
Continued
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals