Transducer Block
December 2009
4-39
For instruments with relay A or C If increasing air
pressure at output A causes the shaft to turn
clockwise, enter Clockwise. If it causes the shaft to
turn counterclockwise, enter Counterclockwise.
For instruments with relay B If decreasing air
pressure at output B causes the shaft to turn
clockwise, enter Clockwise. If it causes the shaft to
turn counterclockwise, enter Counterclockwise.
Lever Style
Enter the lever style (LEVER_STYLE [85.10]) for
rotary actuators as either Pivot Point or Rack and
Pinion.
Lever Arm Length
Defines the lever arm length (MOMENT_ARM [85.11])
for rotary actuators.
Effective Area
Enter the actuator effective area (EFFECTIVE_AREA
[85.2]) in in
2
, cm
2
, or mm
2
.
Air
Select Opens or Closes, indicating the effect of
increasing air pressure (AIR [85.3]) on the valve travel.
Upper Bench Set
Enter the upper actuator operating pressure
(UPPER_BENCH_SET [85.5]).
Lower Bench Set
Enter the lower actuator operating pressure
(LOWER_BENCH SET [85.4]).
Nominal Supply Pressure
Enter the nominal instrument supply pressure
(NOMINAL_SUPPLY PRESSURE [85.6]).
Spring Rate
Enter the actuator spring rate (SPRING_RATE [85.7])
in lbsin or Nm.
Reference
Trim Style 1
Enter the valve trim style (TRIM_STYLE_1 [84.9]).
Trim Style 2
Enter the valve trim style (TRIM_STYLE_2 [84.10]).
Stroking Time Open
Enter the time required to stroke the valve from closed
to open (STROKING_TIME_OPEN [85.8]).
Stroking Time Close
Enter the time required to stroke the valve from open
to close (STROKING_TIME_CLOSE [85.9]).
MAI Channel Map
(TB > Configure/Setup > Detailed Setup > MAI
Channel Map)
Allows the user to specify which transducer block
parameter is available through each of the MAI Block
channels (MAI_CHANNEL_1 through
MAI_CHANNEL_8 [95.1 through 95.8]). Transducer
block parameters available to each channel:
11 = FINAL_VALUE
12 = TRAVEL_TARGET
13 = FINAL_POSITION_VALUE
14 = TRAVEL
15 = SUPPLY_PRESS
16 = ACT_PRESS_A
17 = ACT_PRESS_B
18 = ACT_PRESS_DIFF
19 = DRIVE_SIGNAL
10 = TRAVEL_DEVIATION
11 = TEMPERATURE
12 = CYCLE_COUNT
13 = TRAVEL_ACCUM
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals