EasyManuals Logo
Home>Emerson>Controller>Fisher Fieldvue DVC6030f

Emerson Fisher Fieldvue DVC6030f User Manual

Emerson Fisher Fieldvue DVC6030f
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
DVC6000f Series
March 2006
5-94
Table 5-31. PID Function Block System Parameters Definitions (Continued)
Label
PARAMETER_NAME
DescriptionInitial ValueRange
Block
Mode
RO /
RW
Index
Number
T Auto Extra DT
T_AUTO_EXTRA_DT
90 ALL 0
Data Type: Unsigned8
Allow additional cycle with extra deadtime.
T Auto Hysteresis
T_AUTO_HYSTERESIS
91 ALL 0
Data Type: Unsigned8
Allows calculation of hysteresis based on
CAP_STDDEV
T Aoperiods
T_AOPERIODS
92 RO N/A 0
Data Type: Unsigned8
Actual oscillation periods.