Installation and Configuration
18
Figure 12 Terminal block connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS
NOTE
The installer must provide circuit breaker protection according to local codes. The mains
disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service
space around the UPS or use flexible conduit.
The installer must provide output distribution panels, circuit breaker protection or emergency
disconnects according to local codes. Output circuits must not share a common conduit with
any other wiring.
PD2-CE10HDWRMBSPD2-CE6HDWRMBS