Chapter 9 Specifications 37
Liebert GXT4 UPS 700VA ~ 3000VA (230V) User Manual
Table 9-2 Specifications of GXT4-1500RT230 ~ GXT4-3000RT230 UPS (included the E model)
Parameters
Product model
GXT4-1500RT230 &
GXT4-1500RT230E
(1500VA/1350W)
GXT4-2000RT230 &
GXT4-2000RT230E
(2000VA/1800W)
GXT4-3000RT230 &
GXT4-3000RT230E
(3000VA/2700W)
Dimensions, D
× W × H, in.
(mm)
Unit 19.7 × 16.9 × 3.4 (497 × 430 × 85)
23.7 × 16.9 × 3.4
(602 × 430 × 85)
Shipping 25.5 × 23.9 × 10.6 (647 × 607 × 270)
29.4 × 23.4 × 10.6
(747 × 607 × 270)
Weight, lb (kg)
Unit 51.1 (23.2) 56.1 (25.5) 71.4 (32.4)
Shipping
66.1 (30) E
model:57.3(26)
70.5 (32) E
model:61.7(28)
86 (39) E model:77.2(35)
Input AC
Voltage range
(typical)
230Vac nominal; variable based on output load
90% ~ 100% loading 177Vac/280Vac 196Vac/280Vac
70% ~ 90% loading 168Vac/280Vac 184Vac/280Vac
30% ~ 70% loading 150Vac/280Vac 161Vac/280Vac
0 ~ 30% loading 115Vac/280Vac 115Vac/280Vac
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power
Receptacle
C14 C20
Output AC
Output Receptacles C13 × 6 C13 × 6 + C19 × 1
Voltage 220/230/240Vac (user configurable); ±3%
Waveform Sine wave
Utility (AC) mode
overload
200% for 2 seconds
150% for 50 seconds
150% for 55 seconds
200% for 2 seconds
Battery
Type Valve-regulated, nonspillable, lead acid
Qty × V× Rating 4 × 12V × 7.2Ah 4 × 12V × 9.0Ah 6 × 12V × 9.0Ah
Battery Mfg/Part#
Panasonic/UP-RW1236
CSB/ GP 1272 CSB/UPS
12350
Panasonic/UP-RW1245
CSB/HR1234W HR CSB/ UPS 12460 F2
Back-Up time See Table 9-5
Recharge time
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(Internal Batteries Only)
Environmental
Requirements
Operating
temperature, °F (°C)
32 to 104 (0 to 40); see Table 9-4 - Operating temperature parameters
Storage
temperature, °F (°C)
+5 to +122 (-15 to +50)
Relative humidity 0% to 95%, non-condensing
Operating elevation Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Storage elevation 50,000 ft. (15000m) maximum
Audible noise
< 45dBA at 3ft (1m) rear
< 46 dBA at 3ft. (1m) front
and side
<48dBA max 3ft (1m) front and side
<48dBA max 3ft. (1m) rear
Agency
Safety IEC/EN 62040-1:2008, GS mark
RFI/EMI IEC/EN/AS 62040-2 2nd Ed(Category C2)=CISPR22 Class A
Surge immunity IEC 62040-2 2nd Ed(IEC/EN 61000-4-5)
Transportation ISTA Procedure 1A
Note:
No slide rails assemblies are included in the E model.