Messaging
32
6.3 Customize Messages
Both e-mail and SMS text messages may be custom-
ized to include items such as the IP address or host-
name, event name and a link to the Web card in the
body of the message.
Terminal Emulation (Serial or TCP/IP Connec-
tion) / Telnet
1. Choose Messaging from the Main Menu, then
Email Configuration (or SMS
Configuration).
2. Choose Email (or SMS) Customize Message from the Configuration menu.
3. Choose an option from the Email (or SMS) Customize Message Menu, then enter y (yes) at the
prompt to confirm your choice. Repeat for each item to be included in messages. Refer to the
following guidelines to make changes:
Table 21 E-mail and SMS message guidelines
Parameter Description—if enabled, outgoing messages will include: Defined in:
IP address or
hostname
The IP Address or Hostname of the Web card 5.1 - Boot/IP Settings
Event Description of the SNMP event 9.0 - Support Information
Event Date
& Time
The date & time when the SNMP event occurred
Name The name for the Liebert unit 4.0 - System Information
Contact The contact person or department 4.0 - System Information
Location The location of the Liebert unit 4.0 - System Information
Description Other information about the Liebert unit 4.0 - System Information
Web Link & Port
A clickable link to the Web card through the Web interface 5.1 - Boot/IP Settings
The port number of the SMTP server port
6.1 - E-Mail Configuration
6.2 - SMS Configuration
Event
Consolidation
Enable or disable consolidation of events for e-mail/SMS
notification
6.1 - E-Mail Configuration
6.2 - SMS Configuration
Consolidation
Time Limit
(seconds)
Duration (in seconds) to consolidate events before sending a
notification. Notification will be sent when this threshold is
reached, regardless of event limit. Range: 10 to 120.
Message Consolidation
Time Limit on page 33
Consolidation
Event Limit
Number of events to consolidate before sending a notification.
Notification will be sent when this threshold is reached,
regardless of time limit. Range: 1 to 50.
Message Consolidation
Time Limit on page 33
Email/SMS Customize Message Menu
--------------------------------
1: IP Address 'enabled'
2: Event 'enabled'
3: Event Date & Time 'disabled'
4: Name 'enabled'
5: Contact 'enabled'
6: Location 'enabled'
7: Description 'enabled'
8: Web link & Port 'disabled'
9: Event Consolidation 'enabled'
A: Consolidation Time Limit (seconds) 60
B: Consolidation Event Limit 30
<ESC>: Cancel menu level
Please select a key ?>

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Liebert IntelliSlot IS-WEB485ADPT and is the answer not in the manual?

Emerson Liebert IntelliSlot IS-WEB485ADPT Specifications

General IconGeneral
BrandEmerson
ModelLiebert IntelliSlot IS-WEB485ADPT
CategoryNetwork Card
LanguageEnglish

Related product manuals