What causes pipe rattle in Emerson Liebert XDP Air Conditioner?
- RRachel JonesSep 14, 2025
Pipe rattle in your Emerson Air Conditioner system is caused by loose pipe connections. Check the pipe connections.

What causes pipe rattle in Emerson Liebert XDP Air Conditioner?
Pipe rattle in your Emerson Air Conditioner system is caused by loose pipe connections. Check the pipe connections.
What causes clogged filter dryer and/or impeller in Emerson Liebert XDP?
If the filter dryer and/or impeller is clogged in your Emerson Air Conditioner, it is likely due to debris or other contaminants in the refrigerant. Replace the clogged filter dryer and/or impeller.
What to do if Emerson Liebert XDP Air Conditioner pump will not start or run?
If your Emerson Air Conditioner pump isn't starting or running, here are a few things to check:* Make sure there's chilled water supply to the Liebert XDP.* Ensure all isolation valves on the pump suction and/or discharge are fully open.* Verify the chilled water temperature setpoint is at 50°F (10°C) or lower, and that there's flow on the chilled water side.* Confirm that the Liebert XD cooling modules are on before starting the Liebert XDP.* Check the alarm history for Low Refrigerant Temperature (high dew point), and if necessary, lower the humidity in the conditioned space. (Disconnect must be switched to Off then back On to allow Liebert XDP to reset itself).* Check both differential pressure settings on the pressure switch. They should be within 6 psi, ± 1 psi (41kPa, ±7k...
What to do if Liebert XDP (Pump) of Emerson Air Conditioner suddenly stops?
If the Emerson Air Conditioner pump (Liebert XDP) suddenly stops, consider the following potential causes:* **Low refrigerant temperature:** Check the room's humidity and the placement of remote sensors, ensuring they're not in cold areas with poor airflow. Also, check if the chilled water temperature is too cold or the load is too light.* **Loss of power:** If this is the case, the Liebert XDP will automatically restart once power is restored.* **Clogged filter dryer and/or impeller:** Clean out any debris.* **Leak in system:** Use a refrigerant sniffer to check for leaks and repair them as needed.* **Low chilled water temperature alarm and loss of flow Pump X alarm:** Check the supply chilled water temperature.* **Supply refrigerant sensor failure alarm:** Check the wiring.
| Power Supply | 50/60 Hz (depending on the model) |
|---|---|
| Refrigerant | R410A |
| Compressor Type | Scroll |
| Control System | Liebert iCOM |
| Airflow Configuration | Downflow, Upflow |
Covers hazards like electrical shock, unit falling, and piping rupture.
Details system overview, cooling capacity, and minimum load requirements.
Guidance on unit positioning and clearances for installation.
Covers high-voltage, low-voltage, and sensor wiring.
Specifications for pipe diameters and lengths for refrigerant circuits.
Procedure for evacuating and leak testing the refrigerant system.
Steps for charging the system with R-134a refrigerant.
Accessing and using the diagnostics and service modes for troubleshooting.
Pre-startup checks for refrigerant, valves, and pump rotation.