Integratethemeterwiththecontrolsystem
Procedure
1.Setthechanneltooperateasafrequencyoutput,ifyouhavenotalreadydoneso.
2.SetFrequencyOutputScalingMethod.
Frequency=Flow
Frequencycalculatedfromowrate
Pulses/UnitAuser-speciednumberofpulsesrepresentsoneowunit
Units/PulseApulserepresentsauser-speciednumberofowunits
3.Setadditionalrequiredparameters.
IfyousetFrequencyOutputScalingMethodtoFrequency=Flow,setRateFactorand
FrequencyFactor.
IfyousetFrequencyOutputScalingMethodtoPulses/Unit,denethenumberofpulses
thatwillrepresentoneowunit.
IfyousetFrequencyOutputScalingMethodtoUnits/Pulse,denethenumberofunits
thateachpulsewillindicate.
Frequency=Flow
TheFrequency=Flowoptionisusedtocustomizethefrequencyoutputforyourapplicationwhen
youdonotknowappropriatevaluesforUnits/PulseorPulses/Unit.
IfyouselectFrequency=Flow,youmustprovidevaluesforRateFactorandFrequencyFactor:
RateFactorThemaximumowratethatyouwantthefrequencyoutputtoreport.
Abovethisrate,thetransmitterwillreportA110:Frequency
OutputSaturated.
FrequencyFactorAvaluecalculatedasfollows:
where:
TFactortoconvertselectedtimebaseto
seconds
NNumberofpulsesperowunit,as
conguredinthereceivingdevice
TheresultingFrequencyFactormustbewithintherangeofthefrequencyoutput(0to10,000Hz):
IfFrequencyFactorislessthan1Hz,recongurethereceivingdeviceforahigherpulses/unit
setting.
IfFrequencyFactorisgreaterthan10,000Hz,recongurethereceivingdeviceforalower
pulses/unitsetting.
Tip
IfFrequencyOutputScaleMethodissettoFrequency=Flow,andFrequencyOutputMaximum
PulseWidthissettoanon-zerovalue,MicroMotionrecommendssettingFrequencyFactorto
avaluelessthan200Hz.