Integratethemeterwiththecontrolsystem
2.4.4Faultindicationwiththediscreteoutput
Toindicatefaultsviathediscreteoutput,setparametersasfollows:
▪DiscreteOutputSource=Fault
▪DiscreteOutputFaultAction=None
Note
IfDiscreteOutputSourceissettoFaultandafaultoccurs,thediscreteoutputisalwaysON.The
settingofDiscreteOutputFaultActionisignored.
2.5Conguredigitalcommunications
Display
OFF-LINEMAINT→OFF-LINECONFG→COMM
ProLinkII
ProLink→Conguration→Device
Communicator
5,3,4
DetailedSetup→CongOutputs→HARTOutput
Thedigitalcommunicationsparameterscontrolhowthetransmitterwillcommunicateusingdigital
communications.
TheModel2700transmitterwithintrinsicallysafeoutputssupportsthefollowingtypesofdigital
communications:
▪HART/Bell202overtheprimarymAterminals
▪Modbus/RS-485viatheserviceport
DigitalCommunicationsFaultActionappliestoalltypesofdigitalcommunications.
Note
Theserviceportrespondsautomaticallytoawiderangeofconnectionrequests.Itisnot
congurable.
2.5.1CongureHART/Bell202communications
Display
OFF-LINEMAINT→OFF-LINECONFG→COMM
ProLinkII
ProLink→Conguration→Device→DigitalCommSettings
Communicator
5,3,4
DetailedSetup→CongOutputs→HARTOutput
HART/Bell202communicationsparameterssupportHARTcommunicationwiththetransmitter's
primarymAterminalsoveraHART/Bell202network.
20
MicroMotionModel2700TransmitterswithIntrinsicallySafeOutputs