Integratethemeterwiththecontrolsystem
HI
Theeventwilloccurifthevalueoftheassignedprocessvariable(x)isgreaterthan
thesetpoint(SetpointA),endpointnotincluded.
x>A
LOTheeventwilloccurifthevalueoftheassignedprocessvariable(x)islessthanthe
setpoint(SetpointA),endpointnotincluded.
x<A
IN
Theeventwilloccurifthevalueoftheassignedprocessvariable(x)is“inrange,”
i.e.,betweenSetpointAandSetpointB,endpointsincluded.
A≤x≤B
OUTTheeventwilloccurifthevalueoftheassignedprocessvariable(x)is“outofrange,”
i.e.,lessthanSetpointAorgreaterthanSetpointB,endpointsincluded.
x≤Aorx≥B
3.Assignaprocessvariabletotheevent.
4.Setvaluesfortherequiredsetpoints.
▪ForHIorLOevents,setSetpointA.
▪ForINorOUTevents,setSetpointAandSetpointB.
5.(Optional)Congureadiscreteoutputtoswitchstatesaccordingtoeventstatus.
6.(Optional)Specifytheactionoractionsthatthetransmitterwillperformwhentheevent
occurs.T odothis:
▪WithProLinkII:ProLink→Conguration→DiscreteInput
▪WiththeCommunicator:DetailedSetup→DiscreteActions→AssignDiscretes
OptionsforEnhancedEventAction
Table2-16OptionsforEnhancedEventAction
ActionProLinkIIcodeCommunicatorcode
None(default)
NoneNone
StartsensorzeroStartSensorZeroStartSensorZero
Start/stopalltotalizersStart/StopAllT otalizationStart/StopTotals
ResetmasstotalResetMassTotalResetMassTotal
ResetvolumetotalResetVolumeTotalResetVolumeTotal
Resetgasstandardvolumetotal
ResetGasStdVolumeT otalResetGasStandardVolumeT otal
ResetalltotalsResetAllT otalsResetAllT otals
Resettemperature-correctedvolume
total
ResetAPIRefVolT otalResetCorrectedVolumeT otal
ResetreferencevolumetotalResetCMRefVolT otal
Notavailable
Resetnetmasstotal
ResetCMNetMassTotal
Notavailable
Resetnetvolumetotal
ResetCMNetVolT otal
Notavailable
Incrementcurve
IncrementCurrentCMCurve
Notavailable
StartmetervericationtestStartMeterVerication
Notavailable
CongurationandUseManualSupplement