Integratethemeterwiththecontrolsystem
TheModel2700transmittersupportstwoeventmodels:
Basiceventmodel
Enhancedeventmodel
2.6.1Congureabasicevent
DisplayNotavailable
ProLinkII
ProLink→Conguration→Events
Communicator
5,6
DetailedSetup→CongEvents
A“basic”eventisusedtoprovidenoticationofprocesschanges.Abasiceventoccurs(isON)
ifthereal-timevalueofauser-speciedprocessvariablemovesabove(HI)orbelow(LO)a
user-denedsetpoint.Youcandeneuptotwobasicevents.Eventstatuscanbequeriedvia
digitalcommunications,andadiscreteoutputcanbeconguredtoreporteventstatus.
Procedure
1.SelectEvent1orEvent2fromEventNumber.
2.SpecifyEventType.
HI
Theeventwilloccurifthevalueoftheassignedprocessvariable(x)isgreaterthan
thesetpoint(SetpointA),endpointnotincluded.
x>A
LOTheeventwilloccurifthevalueoftheassignedprocessvariable(x)islessthanthe
setpoint(SetpointA),endpointnotincluded.
x<A
3.Assignaprocessvariabletotheevent.
4.Setavalueforthesetpoint(SetpointA).
5.(Optional)Congureadiscreteoutputtoswitchstatesaccordingtoeventstatus.
2.6.2Congureanenhancedevent
DisplayNotavailable
ProLinkII
ProLink→Conguration→DiscreteEvents
Communicator
5,5
DetailedSetup→CongDiscreteEvent
An“enhanced”eventisusedtoperformspecictransmitteractionsiftheeventoccurs.An
enhancedeventoccurs(isON)ifthereal-timevalueofauser-speciedprocessvariablemoves
above(HI)orbelow(LO)auser-denedsetpoint,orinrange(IN)oroutofrange(OUT)with
respecttotwouser-denedsetpoints.Youcandeneuptoveenhancedevents.Foreach
enhancedevent,youcanassignoneormoreactionsthatthetransmitterwillperformifthe
enhancedeventoccurs.
Procedure
1.SelectEvent1,Event2,Event3,Event4,orEvent5fromEventName.
2.SpecifyEventType.
26
MicroMotionModel2700TransmitterswithIntrinsicallySafeOutputs