Quick Installation Guide
00825-0100-4004, Rev DB
December 2011
Rosemount 8800D
16
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Rosemount Inc. — Eden Prairie, Minnesota, USA
Emerson Process Management BV - Ede, The Netherlands
Emerson Process Management Flow Technologies Company, Ltd - Nanjing, Jiangsu
Province, P.R. China
Flameproof enclosure Ex d protection type in
accordance with IEC 60079-1, EN 60079-1
Transmitters with Flameproof enclosure type protection shall only be opened when
power is removed.
Closing of entries in the device must be carried out using the appropriate Ex d cable
gland or blanking plug. Unless otherwise marked on housing, the standard conduit entry
thread forms are 1/2-14 NPT.
Type n protection type in accordance with IEC 60079-15, EN 60079-15
Closing of entries in the device must be carried out using the appropriate Ex e or Ex n cable
gland and metal blanking plug or any appropriate ATEX or IECEx approved cable gland and
blanking plug with IP66 rating certified by an EU approved certification body.
European Directive Information
The CE Declaration of Conformity for all applicable European directives for this product can
be found on our website at www.rosemount.com. A hard copy may be obtained by
contacting our local sales office.
ATEX Directive
Rosemount Inc. complies with the ATEX Directive.
European Pressure Equipment Directive (PED)
Rosemount 8800D Vortex Flowmeter Line Size 40 mm to 300 mm
Certificate Number 59552-2009-CE-HOU-DNV
0575
Module H Conformity Assessment
Mandatory CE-marking for flowmeters in accordance with Article 15 of the PED can be
found on the flowtube body.
Flowmeter categories I – III use module H for conformity assessment procedures.
Rosemount 8800 Vortex Flowmeter
Line Size 15 mm and 25 mm
Sound Engineering Practice
Flowmeters that are SEP are outside the scope of PED and cannot be marked for
compliance with PED.