4–20 mA HART entity
parameters
Fieldbus entity
parameters
FISCO input parameters
P
i
(1)
= 1.0 W P
i
(1)
= 1.3 W P
i
(1)
= 5.32 W
C
i
= 0 µF C
i
= 0 µF C
i
= 0 µF
L
i
= 0.97mH L
i
< 10 µH L
i
< 10 µH
(1) Total for transmitter.
ATEX FISCO
IA
Certification No. Baseefa05ATEX0084X
ATEX marking:
II 1 G Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ 60 °C)
2460
Special conditions for safe use (X):
1. When fitted with 90V transient suppressors (T1 option), the
equipment is not capable of passing the 500V isolation test. This
must be taken into account upon installation.
2. The enclosure may be made from aluminum alloy and given a
protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion when located in Zone
0 environment. The polyurethane paint finish may constitute an
electrostatic hazard and must only be cleaned with a damp cloth.
3. When the equipment is installed, particular precautions must be
taken to ensure taking into account the effect of process fluid
temperature, that the ambient temperature of the electrical
housing of the equipment meets the marked protection type
temperature range.
ATEX Type 'n' certification
EN 60079-0: 2012 + A11: 2013
EN 60079-11: 2012
EN 60079-15: 2010
N1
Certification No. Baseefa05ATEX0085X
ATEX marking:
II 3 G Ex nA ic IIC T5 Gc (-50 °C ≤ Ta ≤ 70 °C) 4–20 mA HART
II 3 G Ex nA ic IIC T5 Gc (-50 °C ≤ Ta ≤ 60 °C) Fieldbus
Maximum Working Voltage = 42 VDC 4–20 mA HART
Maximum Working Voltage = 32 VDC Fieldbus
October 2018 Quick Start Guide
Quick Start Guide 33