Integral Flowmeter marked:
II 1/2 G Ex db [ia] IIC T6...T1 Ga/Gb (-50 °C ≤ Ta ≤ 70 °C)
Remote Transmitter marked:
II 2(1) G Ex db [ia Ga] IIC T6 Gb (-50 °C ≤ Ta ≤ 70 °C)
with meter body marked:
II 1 G Ex ia IIC T6...T1 Ga (-50 °C ≤ Ta ≤ 70 °C)
EPL Ga piezo sensor and thermocouple connections.
EPL Gb transmitter enclosure.
2460
42 VDC Max 4–20 mA HART
32 VDC Max Fieldbus
U
m
= 250V
Thermal data:
Ambient temperature
(°C)
Process temperature
(°C)
T-Class sensor (°C)
–50 to +70 –200 to +75 T6
–50 to +70 –200 to +95 T5
–50 to +70 –200 to +130 T4
–50 to +70 –200 to +195 T3
–50 to +70 –200 to +290 T2
–50 to +70 –200 to +427 T1
Installation instructions:
1. The cable and conduit entry devices shall be of a certified
flameproof type Ex d, suitable for the conditions of use and
correctly installed.
2. Unused apertures shall be closed with suitable blanking
elements.
3. When the ambient temperature at the cable or conduit entries
exceed 60 °C, cables suitable for at least 90 °C shall be used.
4. Remote mounted sensor; in type of protection Ex ia IIC, only to
be connected to the associated Model 8800D Vortex Flowmeter
electronics. The maximum allowable length of the
interconnecting cable is 152 m (500 ft).
Special conditions for safe use (X):
1. For information regarding the dimensions of the flameproof
joints, the manufacturer shall be contacted.
October 2018 Quick Start Guide