Table 9-9 Power stage temperature 1 (Pr 7.04) in °C
Table 9-10 Power stage temperature (Oht2)
Additional monitoring is used with drives sizes SP6xxx and SPMxxxx to detect failure of the power stage cooling fan. If this fan fails the monitoring
point used to derive power stage temperature 1 that is nearest the fan will rise temperature above it s normal level, but not above the trip temperature
for power stage. This is detected and can initiate an Oht2 trip. The trip thresholds are show below.
Table 9-11 Power stack temperature 2 (Pr 7.05) in °C
Table 9-12 Power stack temperature 3 (Pr 7.36) in °C
The control board temperature is also monitored and displayed in Pr 7.06. If the temperature displayed exceeds 92°C an O.Ctl trip is initiated, and this
trip can only be reset if the temperature falls below 87°C. If the temperature exceeds 85°C a "hot" alarm is displayed. If the temperature is outside the
range from -20°C to 150°C it is assumed that the monitoring thermistor has failed and an HF29 hardware fault trip is initiated.
Drive cooling fan
The drive cooling fan is controlled by the temperature from monitoring points and other actions as follows:
1. If Pr 6.45 = 1 the fan is at full speed for at least 10s.
2. If an option module indicates that it is too hot the fan is at full speed for at least 10s.
3. For drive sizes SP0xxx to SP2xxx the fan is at full speed if the drive is enabled and the highest power circuit temperature (Pr 7.04 or Pr 7.05) or
the temperature calculated for the case of the IGBT package exceed the threshold for the drive. The fan is at its low speed if this temperature falls
to 5°C below the threshold or the drive is disabled and the temperature is below the alarm level for Pr 7.04 and Pr 7.05.
4. For drive sizes SP3xxx to SPMxxxx the fan speed is controlled above its minimum level if the drive is enabled and the highest power circuit
temperature (Pr 7.04, Pr 7.05 or Pr 7.36) or the temperature calculated for the case of the IGBT package exceed the lower threshold for the drive.
The maximum fan speed is reached when the highest of these temperatures exceeds the upper threshold. The fan is at its minimum speed if the
drive is disabled and the temperature is below the alarm level for Pr 7.04, Pr 7.05 and Pr 7.36.
The thresholds are given in Table 9-13 in °C.
Drive size Trip temperature Trip reset temperature Alarm temperature
SP0xxx TBA TBA TBA
SP1xxx 110 105 100
SP2xxx 115 110 100
SP3xxx 120 115 100
SP4xxx 72 67 68
SP5xxx 72 67 68
SP6xxx 92 87 85
SPMxxxx 96 91 88
Drive size Trip temperature
SP6xxx 67
SPMxxxx 71
Drive size Trip temperature Trip reset temperature Alarm temperature
SP0xxx TBA TBA TBA
SP1xxx 92 87 85
SP2xxx 100 95 95
SP3xxx 98 93 94
SP4xxx 78 73 72
SP5xxx 78 73 72
SP6xxx 78 73 72
SPMxxxx 78 73 72
Drive size Trip temperature Trip reset temperature Alarm temperature
SP0xxx TBA TBA TBA
SP1xxx N/A N/A N/A
SP2xxx N/A N/A N/A
SP3xxx N/A N/A N/A
SP4xxx N/A N/A N/A
SP5xxx N/A N/A N/A
SP6xxx 85 80 80
SPMxxxx 125 100 120