EasyManuals Logo

Emerson Unidrive M201 Installation Guide

Emerson Unidrive M201
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Unidrive M / HS Frame 7 to 10 Power Installation Guide 13
Issue Number: 5
Safety information
Product information
Mechanical installation Electrical installation Technical data UL listing information
2.4 Ratings
Table 2-1 200 V drive ratings, cable sizes and fuse ratings
Table 2-2 400 V drive ratings, cable sizes and fuse ratings
* These fuses are fast acting.
** These ratings are for 2 kHz switching frequency. For ratings at 3 kHz switching frequency refer to the Power and
current ratings in section 5.1.2
Power and current ratings (Derating for switching frequency and
temperature)
on page 90.
Fuses
The AC supply to the drive must be installed with suitable protection against overload and
short-circuits. The following section shows recommended fuse ratings. Failure to observe
this requirement will cause risk of fire.
Nominal cables sizes below are based on the cable installation method B2 (ref: IEC60364-
5-52:2001) unless otherwise specified, and are provided as a guide only. Ensure cables
used suit local wiring regulations.
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty Heavy Duty
European USA
IEC UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
230 V
Motor
power
@
230 V
Max.
cont.
output
current
Nom
power
@
230 V
Motor
power
@
230 V
3ph Nom
Class
Nom
Class
AA A
mm
2
mm
2
AWG
or
kcmil
AWG
or
kcmil
AkWhp A kWhp
07200610 67 80
gG
80
CC,
J or T*
35 35 2 2 75 18.5 25 61 15 20
07200750 84 100 100 35 35 1 1 94 22 30 75 18.5 25
07200830 105 125 125 70 70 1/0 1/0 117 30 40 83 22 30
08201160 137 200
gR
200
HSJ
95 95 3/0 3/0 149 37 50 116 30 40
08201320 166 200 225 2 x 70 2 x 70 2 x 1 2 x 1 180 45 60 132 37 50
09201760 205 250
gR
250
HSJ
2 x 70
(B1)
2 x 95
(B2)
2 x 2/0 216 55 75 176 45 60
09202190 260 315 300
2 x 95
(B1)
2 x 120
(B2)
2 x 4/0 266 75 100 219 55 75
10202830 305 400
gR
400
HSJ
2 x 120
(B1)
2 x 120
(C)
2 x
300
2 x 250 325 90 125 283 75 100
10203000 361 450 450
2 x 150
(C)
2 x
300
2 x 300 360 110 150 300 90 125
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty Heavy Duty
European USA
IEC UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
400 V
Motor
power
@
460 V
Max.
cont.
output
current
Nom
power
@
400 V
Motor
power
@
460 V
3ph Nom
Class
Nom
Class
AA A
mm
2
mm
2
AWG
or
kcmil
AWG
or
kcmil
AkWhpAkWhp
07400660 74 100
gG
80
CC,
J or
T*
35 35 1 1 79 37 60 66 30 50
07400770 88 100 100 50 50 2 2 94 45 60 77 37 60
07401000 105 125 125 70 70 1/0 1/0 112 55 75 100 45 75
08401340 155 250
gR
225
HSJ
2 x 50 2 x 50 2 x 1 2 x 1 155 75 100 134 55 100
08401570 177 250 225 2 x 70 2 x 70 2 x 1/0 2 x 1/0 184 90 150 157 75 125
09402000 232
315 gR
300
HSJ
2 x 70
(B1)
2 x 95
(B2)
2 x 3/0 2 x 2/0 221 110 150 200** 90 150
09402240 267 350
2 x 95
(B1)
2 x 120
(B2)
2 x 4/0 2 x 4/0 266** 132 200 224** 110 150
10402700 332 400
gR
400
HSJ
2 x 120
(C)
2 x 120
(B2)
2 x 300 2 x 250 320 160 250 270 132 200
10403200 397 450 450
2 x 150
(C)
2 x 150
(B2)
2 x 350 2 x 300 361 200 300 320** 160 250
WARNING
NOTE
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 13 Tuesday, May 24, 2016 11:52 AM

Table of Contents

Other manuals for Emerson Unidrive M201

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Unidrive M201 and is the answer not in the manual?

Emerson Unidrive M201 Specifications

General IconGeneral
BrandEmerson
ModelUnidrive M201
CategoryController
LanguageEnglish

Related product manuals