14 Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
Table 2-3 575 V drive ratings, cable sizes and fuse ratings
* These fuses are fast acting.
Table 2-4 690 V drive ratings, cable sizes and fuse ratings
* These fuses are fast acting.
Table 2-5 Protective ground cable ratings
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty Heavy Duty
European USA
IEC UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
575 V
Motor
power
@
575 V
Max.
cont.
output
current
Nom
power
@
575 V
Motor
power
@
575 V
3ph Nom
Class
Nom
Class
AA A
mm
2
mm
2
AWG AWG A kW hp A kW hp
07500440 45 50
gG
50
CC,
J or T*
16 16 4 4 53 45 50 44 30 40
07500550 62 80 80 25 25 3 3 73 55 60 55 37 50
08500630 83 125
gR
100
HSJ
35 35 1 1 86 75 75 63 45 60
08500860 104 160 150 50 50 1 1 108 90 100 86 55 75
09501040 166 150
gR
150 HSJ
2 x 70
(B2)
2 x 35
(B2)
2 x 1
2 x 3 125 110 125 104 75 100
09501310 166 200 175 HSJ
2 x 50
(B2)
2 x 1 155 110 150 131 90 125
10501520 197
250 gR 250 HSJ
2 x 70
(B2)
2 x 70
(B2)
2 x
2/0
2 x
2/0
200 130 200 152 110 150
10501900 218
2 x 95
(B2)
200 150 200 190 132 200
Model
Max.
cont.
input
current
Fuse
Nominal cable size
Normal Duty Heavy Duty
European USA
IEC UL
Input Output Input Output
Max.
cont.
output
current
Nom
power
@
690 V
Motor
power
@
690 V
Max.
cont.
output
current
Nom
power
@
690 V
Motor
power
@
690 V
3ph Nom
Class
Nom
Class
AA A
mm
2
mm
2
AWG AWG A kW hp A kW hp
07600190 20 25
gG
25
CC,
J or
T*
10 10 8 8 23 18.5 25 19 15 20
07600240 26 32 30 10 10 6 6 30 22 30 24 18.5 25
07600290 31 40 35 10 10 6 6 36 30 40 29 22 30
07600380 39 50 50 16 16 4 4 46 37 50 38 30 40
07600440 44 50 50 16 16 4 4 52 45 60 44 37 50
07600540 62 80 80 25 25 3 3 73 55 75 54 45 60
08600630 83 125
gR
100
HSJ
50 50 2 2 86 75 100 63 55 75
08600860 104 160 150 70 70 1/0 1/0 108 90 125 86 75 100
09601040 149 150
gR
150
HSJ
2 x 50
(B2)
2 x 35
(B2)
2 x 1 2 x 3 125 110 150 104 90 125
09601310 171 200 200
2 x 70
(B2)
2 x 50
(B2)
2 x 1/0 2 x 1 155 132 175 131 110 150
10601500 202 225 gR
250 HSJ
2 x 70
(B2)
2 x 70
(B2)
2 x 2/0 2 x 1/0 172 160 200 150 132 175
10601780 225 250 gR
2 x 95
(B2)
2 x 3/0 2 x 2/0 197 185 250 178 160 200
Refer to Chapter 5.1 Drive technical data on page 88 for maximum fuse rating, maximum
cable size and peak currents.
Input phase conductor size Minimum ground conductor size
10 mm
2
Either 10 mm
2
or two conductors of the same cross-sectional area as the input
phase conductor
> 10 mm
2
and 16 mm
2
The same cross-sectional area as the input phase conductor
> 16 mm
2
and 35 mm
2
16 mm
2
> 35 mm
2
Half of the cross-sectional area of the input phase conductor
NOTE
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 14 Tuesday, May 24, 2016 11:52 AM

Table of Contents

Other manuals for Emerson Unidrive M201

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Unidrive M201 and is the answer not in the manual?

Emerson Unidrive M201 Specifications

General IconGeneral
BrandEmerson
ModelUnidrive M201
CategoryController
LanguageEnglish

Related product manuals