This parameter is used to display the error code if an EtherNet/IP configuration error
occurs.
This parameter shows the EtherNet/IP cyclic data transfer rate.
This timeout is defined by the EtherNet/IP protocol and is configured in the PLC master.
The interface will monitor the data traffic and if data is not received within the specified
time, it will perform the requested action. This indicates that the interface has detected
Value Text Description
0 No error No error
1 RPI event dst RPI timeout event destination not valid
2 RPI event type RPI timeout event type not valid
3 IDLE event dst PLC IDLE event destination not valid
4 IDLE event type PLC IDLE event type not valid
5 Input mapping Input mapping parameter not valid
6 Output mapping Output mapping parameter not valid
7 In cons trig pr Input consistency trigger parameter not valid
8 Out cons trig pr
Output consistency trigger parameter not valid
S.20.007 Cyclic data transfers per second
Minimum 0 Maximum 65535
Default Units Messages/s
Type 16 Bit Volatile Update Rate Background
Display Format None Decimal Places 0
Coding RO, ND, NC, PT, BU
S.20.011 RPI timeout action
Minimum 0 Maximum 4
Default 3 Units
Type 8 Bit User Save Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/
IP interface enable
Display Format None Decimal Places 0
Coding RW, TE, BU
Value Text Description
0 Trip Trip drive with Slx.Er and sub-trip code
1 Send flt values Send configured fault values to the output parameters
2 Clear output
PLC output parameters will have their values set to
zero
3 Hold last Hold the last value in output parameters
4No Action
No action with output parameters