96 SI-Ethernet User Guide
Issue: 1
This parameter defines the destination slot to trigger the event upon a PLC idle event.
Defines the event to trigger in the specified destination (PLC idle event destination
(S.20.016)) upon a PLC idle event.
S.20.016 PLC idle event destination
Minimum 0 Maximum 4
Default 0 Units
Type 8 Bit User Save Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/
IP interface enable
Display Format None Decimal Places 0
Coding RW, TE, BU
Value Text Description
0 This slot Trigger event in this slot
1 Slot 1 Trigger event in slot 1
2 Slot 2 Trigger event in slot 2
3 Slot 3 Trigger event in slot 3
4 Slot 4 Trigger event in slot 4
This feature is not yet implemented.
S.20.017 PLC idle event type
Minimum 0 Maximum 5
Default 0 Units
Type 8 Bit User Save Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/
IP interface enable
Display Format None Decimal Places 0
Coding RW, TE, BU
Value Text Description
0 No event No event
1 Trigger Event Trigger module Event
2 Trigger Event 1 Trigger module Event 1
3 Trigger Event 2 Trigger module Event 2
4 Trigger Event 3 Trigger module Event 3
5 Trigger Event 4 Trigger module Event 4
This feature is not yet implemented.
NOTE
NOTE