11 – 17
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Trip Message Cause(s) Notes
(T153) Trip: Out Of Range: Blower 4
Phase C Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T154) Trip: Out Of Range: Blower 4
ODE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T155) Trip: Out Of Range: Blower 4
DE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T156) Trip: Out Of Range: Blower 4
Motor Amps
Motor Amps input is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T157) Trip: Unassigned
(T158) Trip: Unassigned
(T159) Trip: Unassigned