11 – 16
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Trip Message Cause(s) Notes
(T140) Trip: Out Of Range: Blower 3
Discharge Pressure
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T141) Trip: Out Of Range: Blower 3
Discharge Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
(T142) Trip: Out Of Range: Blower 3
Phase A Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T143) Trip: Out Of Range: Blower 3
Phase B Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T144) Trip: Out Of Range: Blower 3
Phase C Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T145) Trip: Out Of Range: Blower 3
ODE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T146) Trip: Out Of Range: Blower 3
DE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T147) Trip: Out Of Range: Blower 3
Motor Amps
Motor Amps input is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T148) Trip: Out Of Range: Blower 4
Suction Pressure
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T149) Trip: Out Of Range: Blower 4
Discharge Pressure
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T150) Trip: Out Of Range: Blower 4
Discharge Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
(T151) Trip: Out Of Range: Blower 4
Phase A Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T152) Trip: Out Of Range: Blower 4
Phase B Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.