11 – 15
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Trip Message Cause(s) Notes
(T127) Trip: Out Of Range: Blower 1
ODE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T128) Trip: Out Of Range: Blower 1
DE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T129) Trip: Out Of Range: Blower 1
Motor Amps
Motor Amps input is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T130) Trip: Out Of Range: Blower 2
Suction Pressure
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T131) Trip: Out Of Range: Blower 2
Discharge Pressure
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T132) Trip: Out Of Range: Blower 2
Discharge Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
(T133) Trip: Out Of Range: Blower 2
Phase A Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T134) Trip: Out Of Range: Blower 2
Phase B Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T135) Trip: Out Of Range: Blower 2
Phase C Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Winding Temperatures are
being monitored.
(T136) Trip: Out Of Range: Blower 2
ODE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T137) Trip: Out Of Range: Blower 2
DE Temperature
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Active if Bearing Temperatures are
being monitored.
(T138) Trip: Out Of Range: Blower 2
Motor Amps
Motor Amps input is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
(T139) Trip: Out Of Range: Blower 3
Suction Pressure
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA