EasyManua.ls Logo

Emerson Wireless 1410 Gateway - Page 24

Emerson Wireless 1410 Gateway
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
should be terminated at both ends (Figure 3-8). However termination should only be used
with high data rates (above 115 kbps) and long cable runs.
Figure 3-8: Typical Half Duplex (2-wire) Network
Up to 4000 ft. (1220 m)
Device 1
A
B
Terminators required
only for high data
rates and long cable
runs
Device N
(up to 32
possible)
Device 2
A
Tx line
B
Rx line
3.4.5 Power
The Gateway is designed to be powered by 24 VDC (nominal) Class 2 supply and requires
250 mA of current. The positive and negative connections are depicted on the diagram
shown in Figure 3-6.
The wiring should include an external power shut-off switch or circuit breaker located near
the Gateway.
Note
Using an uninterruptible power supply is recommended to ensure availability should there
be a loss of power.
Installation Reference Manual
September 2020 00809-0200-4410
24 Emerson.com/Rosemount

Table of Contents

Related product manuals