Standards:
FM Class 3600 – 2011, FM Class 3611 – 2004, FM Class 3616 – 2011, UL 50 -
11
th
Ed, ANSI/ISA 61010-1 - 2012
Markings:
NI CL 1, DIV 2, GP A, B, C, D T4; Suitable for use in CL II, III, DIV 2, GP F, G T4;
T4 (–40 °C ≤ T
a
≤ 60 °C) Nonincendive outputs to remote antenna when
connected per Rosemount drawing 01420-1011; Type 4X
Special Conditions for Safe Use (X):
1. Explosion Hazard. Do not disconnect equipment when a flammable or combustible
atmosphere is present.
B.7 Canada
N6 Canada Division 2
Certificate:
CSA 70010780
Standards:
CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA Std C22.2 No. 94-M91
(R2001), CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 213-M1987,
CSA C22.2 No. 61010-1 - 2012
Markings:
Suitable for Class 1, Division 2, Groups A, B, C, and D, T4; when connected
per Rosemount drawing 01420-1011; Type 4X
Special Conditions for Safe Use (X):
1. Explosion Hazard. Do not disconnect equipment when a flammable or combustible
atmosphere is present.
B.8 Europe
N1 ATEX Type n
Certificate:
Baseefa07ATEX0056X
Standards:
EN 60079-0: 2012, EN 60079-15: 2010
Markings:
II 3 G Ex nA IIC T4 Gc, T4(–40 °C ≤ T
a
≤ +65 °C), V
MAX
= 28Vdc
Special Conditions for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test required by
clause 6.5.1 of EN 60079-15:2010. This must be taken into account when installing
the equipment.
2. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic
charge build-up, it must not be rubbed with a dry cloth or cleaned with solvents.
ND ATEX Dust
Certificate:
Baseefa07ATEX0057X
Standards:
EN 60079-0: 2012, EN 60079-31: 2009
Product Certifications Reference Manual
September 2020 00809-0200-4420
76 Emerson.com/Rosemount