4 Add and Install the Wireless Devices
The Wireless Devices can be added to their relevant RCCs, either by pressing the
devices log on buttons or by entering the devices unique ident number. If
adding by ident, always make a note of the devices ident numbers and device
type prior to installation and refer to the Programming Manual (MK98) for
further details.
Note: Ensure the Wireless Devices are powered before logging on to the system.
See the relevant installation guide for more information.
To add devices by log on;
From Front Display Add New Device Select Desired
RCC 01 Set Loop 1
. Addr 003 Add By Log On Press Dev Log On ‘press the devices
log on button, followed by Add Dev 03456 Y? New Addr L1 A003.
To Exit
The device has now been added to the Radio Hub and should be installed in its
location, prior to the next step of assigning the device to its relevant RCC. See
the relevant devices installation instructions, for more information.