©2018 EMS Ltd. All rights reserved. Page 15 of 24 TSD115 Iss2 17/09/2018 AJM
The display will change and allow a text description to be allocated for the cause and eect rule
written. An example is shown below.
Enter the required text to identify the rule and click the ‘Finish button once complete.
The rules for the system will be displayed under the cause and eect icon on the Loop Explorer
front display. They will be individually identiable via the text description allocated. An example
is shown below.
Repeat the above programming for each of the Wireless RIMs on the system which are required to
follow individual zone activations.
2
1

Other manuals for EMS FIRECELL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EMS FIRECELL and is the answer not in the manual?

EMS FIRECELL Specifications

General IconGeneral
Frequency868 MHz
Operating Temperature-10°C to +55°C
CommunicationWireless
ComplianceEN54-25
Devices SupportedSounders
Power SupplyLithium battery
Humidity RangeUp to 95% RH, non-condensing
CompatibilityEMS Firecell System
TypeWireless Fire Alarm