Description of device parameters Deltabar FMD71, FMD72
26
Factory setting • 100.0 % in Level measuring mode
• URL Sensor or according to ordering information in Pressure measuring mode
Get LRV (015)
Navigation Expert → Output → Current Output → Get LRV (015)
Write permission Operators/Service engineers/Expert
Description Setting lower range value. The pressure for the lower current value (4 mA) is present at
the device. Use the "Confirm" option to assign the lower current value to the applied
pressure value.
Prerequisite Pressure measuring mode
Options • Cancel
• Confirm
Factory setting Cancel
Get URV (016)
Navigation Expert → Output → Current Output → Get URV (016)
Write permission Operators/Service engineers/Expert
Description Setting upper range value. The pressure for the upper current value (20 mA) is present at
the device. Use the "Confirm" option to assign the applied pressure value to the upper
current value.
Prerequisite Pressure measuring mode
Options • Cancel
• Confirm
Factory setting Cancel
Damping (017)/(184)
Navigation Expert → Measurement → Basic Setup → Damping (017)/(184)
Write permission Operators/Service engineers/Expert
(if the "Damping" DIP switch is set to "on")