Description of device parameters Deltabar FMD71, FMD72
44
Prerequisite "Simulation Mode" = Alarm/Warning
Value at switch-on 484 (Simulation active)
Direct access (119)
Navigation Expert → Direct access (119)
Write permission Expert
Description Enter the direct access code to go directly to a parameter.
Options Enter the desired parameter code.
Note For direct access, it is not necessary to enter leading zeros.
Factory setting 0
Lock Switch (120)
Navigation Expert → System → Lock Switch (120)
Write permission Expert
Description Displays the status of DIP switch 1 on the electronic insert. You can lock or unlock
parameters relevant to the measured value with DIP switch 1. If operation is locked by
means of the "Operator Code" (021) parameter, you can only unlock operation again by
means of this parameter.
Display On (locking switched on)
Off (locking switched off)
Factory setting Off (locking switched off)
Electr.serial no (121)
Navigation Expert → System → Instrument info → Electr. Serial No. (121)
Write permission No write permissions. Parameter is read only.
Description Displays the serial number of the main electronics (11 alphanumeric characters).
Sens. Ser. No HP (122)