Commissioning Deltabar M 4...20 mA HART
24 Endress+Hauser
Pressure unit selection
5.3 Position zero adjustment
The pressure resulting from the orientation of the device can be corrected here.
Parameter name Description
Press. eng. unit (125)
Selection
Menu path: Setup
Press. eng. unit
Select the pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and displayed
with the new unit.
Options:
mbar, bar
mmH2O, mH2O, inH2O
•ftH2O
Pa, kPa, MPa
•psi
•mmHg, inHg
•kgf/cm
2
Factory setting:
mbar or bar depending on the sensor nominal measuring range, or as per order specifications
Parameter name Description
Corrected press.
(172)
Display
Menu path:
Setup Corrected
press.
Displays the measured pressure after sensor trim and position adjustment.
!
Note!
If this value is not equal to "0", it can be corrected to "0" by the position adjustment.
Pos. zero adjust (007)
Selection
Menu path:
Setup Pos. zero adjust
Position zero adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known.
Example:
Measured value = 2.2 mbar (0.033 psi)
You correct the measured value via the "Pos. zero adjust" parameter with the "Confirm"
option. This means that you assign the value 0.0 to the pressure present.
Measured value (after pos. zero adjust) = 0.0 mbar
The current value is also corrected.
Options
•Confirm
Abort
Factory setting:
Abort