Deltapilot M 4...20 mA HART Installation
Endress+Hauser 11
4.5.1 General installation instructions
Do not clean or touch process isolating diaphragms with hard or pointed objects.
The process isolating diaphragm in the rod and cable version is protected against mechanical
damage by a plastic cap.
If a heated Deltapilot M is cooled during the cleaning process (e.g. by cold water), a vacuum
develops for a short time, whereby moisture can penetrate the sensor through the pressure
compensation (1). If this is the case, mount the Deltapilot M with the pressure compensation
(1) pointing downwards.
Keep the pressure compensation and GORE-TEX
®
filter (1) free from contamination.
The device must be installed as follows in order to comply with the cleanability requirements
of the ASME-BPE (Part SD Cleanibility).:
4.5.2 FMB50
Level measurement
Always install the device below the lowest measuring point.
Do not install the device at the following positions:
in the filling curtain
in the tank outflow
in the suction area of a pump