Electrical connection Deltapilot M 4...20 mA HART
20 Endress+Hauser
5.1.3 Devices with valve connector
A0023097
Fig. 6: BN = brown, BU = blue, GNYE = green/yellow
A Electrical connection for devices with valve connector
B View of the connection on the device
Material: PA 6.6
5.2 Connecting the measuring unit
5.2.1 Supply voltage
Taking 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the test terminals without interrupting the
measurement. To keep the corresponding measured error below 0.1%, the current measuring
device should exhibit an internal resistance of < 0.7 .
5.2.2 Terminals
Supply voltage and internal ground terminal: 0.5 to 2.5 mm
2
(20 to 14 AWG)
External ground terminal: 0.5 to 4 mm
2
(20 to 12 AWG)
5.2.3 Cable specification
Endress+Hauser recommends using twisted, shielded two-wire cables.
+
21
+
AB
BU BN GNYE
2
1
3
+
Electronic version
4 to 20 mA HART,
for non-hazardous areas
11.5 to 45 V DC
(versions with plug-in connector 35 V DC)