Operating example: User-definable parameters
Example: setting "Set URV" parameter from 100 mbar (1.5 psi) to 50 mbar (0.75 psi).
Language 000 Operation
1 English "English" is set as the menu language (default value). A in front
of the menu text indicates the active option.
Deutsch
2 Deutsch Select "Deutsch" with or .
English
3 Deutsch 1. Confirm your choice with . A in front of the menu text
indicates the active option ("Deutsch" is now selected as the
menu language).
2. Exit the edit mode for the parameter with .
English
Set URV 014 Operation
The local display shows the parameter to be changed. The value
highlighted in black can be changed. The "mbar" unit is specified
in another parameter and cannot be modified here.
1100.000mbar
1. Press or to get to the editing mode.
2. The first digit is highlighted in black.
2 1 00 . 000 mbar
1. Use to change "1" to "5".
2. Confirm "5" with . The cursor jumps to the next position
(highlighted in black).
3. Confirm "0" with (second position).
3 5 00 . 000 mbar
The third position is highlighted in black and can now be edited.
4500 .000 mbar
1. Switch to the "" symbol with the key.
2. Use to save the new value and exit the editing mode.
See next graphic.
550 .000 mbar