Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Level measurement (FF configuration program)
Endress+Hauser 17
5.2.2 Calibration without reference pressure – dry calibration
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of
1000 liters (264 US gal) corresponds to a pressure of 450 mbar (6.75 psi). The minimum volume of
0 liters corresponds to a pressure of 50 mbar (0.75 psi) since the device is mounted below the level
lower-range value.
Prerequisite:
The measured variable is in direct proportion to the pressure.
This is a theoretical calibration i.e. the pressure and volume values for the lower and upper
calibration point must be known.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P) or Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
The values entered for Empty Calib. Level Easy/EMPTY_CALIBRATION_EASY and Full Calib.
Level Easy/FULL_ CALIBRATION_EASY must be at least 1 % apart for the "Level easy pressure"
level mode. The value will be rejected with a warning message if the values are too close together.
Further limit values are not checked; i.e. the values entered must be appropriate for the sensor
and the measuring task so that the measuring device can measure correctly.
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero.
For information on how to perform position adjustment, see also ä 59,
"Pos. Zero Adjust/ZERO_POSITION_ ADJUST".
Description
1 Deltabar S: Before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA00301P.
P01-PMC71xxx-19-xx-xx-xx-008
Fig. 3: Calibration without reference pressure –
dry calibration
1 See Table, Step 10.
2 See Table, Step 9.
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 The following options are available for performing
position adjustment:
By means of the parameters
Pos.Zero Adjust/ZERO_POSITION_ADJUST
( ä 59) or
Pos. Input Value/POSITION_INPUT_VALUE
( ä 59) or
Calib. Offset/CALIBRATION_OFFSET ( ä 59).
1000 l
50 mbar
0l
450 mbar