Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
206 Endress+Hauser
Table 33: OPERATING MENU DIAGNOSTICS SIMULATION
Parameter name Description
SIMULATION MODE (413)
Selection
Switch on simulation and select simulation type.
Any simulation running is switched off if the measuring mode or level mode is changed.
Options:
•None
Pressure, see also this table, parameter description for SIM. PRESSURE.
Flow (only differential pressure transmitter), see also this table, parameter
description for SIM. FLOW VALUE.
Level, see also this table, parameter description for SIM. LEVEL.
Tank content, see also this table, parameter description for SIM. TANK CONT.
Alarm/warning, see also this table, parameter description for SIM. ERROR NO.
P01-xMD7xxxx-05-xx-xx-en-004
Factory setting:
None
SIM. PRESSURE (414)
Entry
Enter the simulation value.
See also SIMULATION MODE.
Prerequisite:
SIMULATION MODE = Pressure
Factory setting:
Current pressure measured value
SIM. FLOW VALUE (639)
Entry
Enter the simulation value.
See also SIMULATION MODE.
Prerequisite:
MEASURING MODE = Pressure and SIMULATION MODE = Flow
MEASURING MODE = Flow and SIMULATION MODE = Flow
SIM. LEVEL (714)
Entry
Enter the simulation value.
See also SIMULATION MODE.
Prerequisite:
MEASURING MODE = Level and SIMULATION MODE = Level
SIM. TANK CONT. (715)
Entry
Enter the simulation value.
See also SIMULATION MODE.
Prerequisites:
MEASURING MODE = Level, LEVEL MODE = Pressure linearized and SIMULATION
MODE = Tank content
MEASURING MODE = Level, LEVEL MODE = Height linearized and SIMULATION
MODE = Tank content
SIM. ERROR NO. (476)
Entry
Enter the message number.
See also SIMULATION MODE.
See also these Operating Instructions, Section 12.1 "Messages", "Code" table column.
Prerequisite:
SIMULATION MODE = Alarm/warning
Factory setting:
613 (simulation active)
P
PV
Simulation value pressure
Transducer Block
Simulation value level
Simulation value tank content
Simulationvalue flow
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim