Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
208 Endress+Hauser
SELECT ALARMTYPE
(595) – Entry
(600) – Selection
Selection
For "Error"-type messages, you can decide whether the device should behave as in the
event of an alarm (A) or as in the event of a warning (W). See also ERROR No.
See also these Operating Instructions, Section 12.2 "Response of outputs to errors".
Options:
Alarm (A): the process variable in question is transmitted with the status BAD.
Warning (W): device continues measuring
Local operation:
1. Enter the corresponding message number for ERROR No. field.
2. Select "Alarm" or "Warning" option.
FieldCare
1. Enter the corresponding message number via the ERROR No. parameter.
2. Use the SELECT ALARMTYPE parameter to select the "Alarm" or "Warning" option.
ALARM DELAY (336)
Entry
Enter the alarm response time for all "Error"-type messages.
!
Note!
There is no alarm if the cause of the error is eliminated within the alarm delay time.
Input range:
0 to 100 s
Factory setting:
0.0 s
ALARM DISPL. TIME (480)
Entry
Enter the alarm delay time for all "Error"-type messages. Once the cause of the error is
rectified, the alarm display time starts running.
!
Note!
The following applies if the setting for ACK. ALARM MODE = On
If an alarm appears and the alarm display time elapses before the alarm has been
acknowledged, the message is cleared once it has been acknowledged.
See also these Operating Instructions, Section 12.3 "Confirming messages".
Input range:
0 to 999.9 s
Factory setting:
0.0 s
Table 35: OPERATING MENU DIAGNOSTICS USER LIMITS
Parameter name Description
Pmin ALARM WINDOW
(332)
Entry
Customer-specific process monitoring – enter lower pressure limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 12.1 "Messages" Table, code E730 and
Section 12.2 "Response of outputs to errors".
Factory setting:
Low sensor limit •1.1
(For the low sensor limit, see PRESS. SENS LOLIM.)
Pmax ALARM WINDOW
(333)
Entry
Customer-specific process monitoring – enter upper pressure limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 12.1 "Messages" Table, code E731 and
Section 12.2 "Response of outputs to errors".
Factory setting:
High sensor limit • 1.1
(For the high sensor limit, see PRESS. SENS HILIM.)
Table 34: OPERATING MENU DIAGNOSTICS MESSAGES