Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Level measurement (FF configuration program)
Endress+Hauser 21
5.3.2 Calibration without reference pressure – dry calibration
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of
1000 liters (264 US gal) corresponds to a level of 4.5 m (15 ft). The minimum volume of 0 liters
corresponds to a level of 0.5 m (1.6 ft) since the device is mounted below the level lower-range
value. The density of the fluid is 1 kg/dm
3
.
Prerequisite:
The measured variable is in direct proportion to the pressure.
This is a theoretical calibration i.e. the height and volume values for the lower and upper
calibration point must be known.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P) or Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
For the "Level easy pressure" level mode, the values entered for Empty Calib. Level Easy/
EMPTY_CALIBRATION_EASY and Full Calib. Level Easy/FULL_ CALIBRATION_EASY must be
at least 1 % apart. The value will be rejected with a warning message if the values are too close
together. Further limit values are not checked; i.e. the values entered must be appropriate for the
sensor and the measuring task so that the measuring device can measure correctly.
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero.
For information on how to perform position adjustment, see also ä 59,
"Pos. Zero Adjust/ZERO_POSITION_ ADJUST".
Description
1 Deltabar S: Before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA00301P.
P01-PMC71xxx-19-xx-xx-xx-009
Fig. 7: Calibration without reference pressure –
dry calibration
1 See Table, Step 10.
2 See Table, Steps 12 and 13.
3 See Table, Steps 14 and 15.
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 The following options are available for performing
position adjustment:
By means of the parameters
Pos.Zero Adjust/ZERO_POSITION_ADJUST
( ä 59) or
Pos. Input Value/POSITION_INPUT_VALUE
( ä 59) or
Calib. Offset/CALIBRATION_OFFSET ( ä 59).
1000 l
0.5 m
4.5 m
0l
r =1
kg
dm
3