Troubleshooting Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
210 Endress+Hauser
Diagnostic Transducer Block (FF configuration program):
The Alarm Status/ALARM_STATUS parameter displays the message with the highest priority.
This parameter is displayed in the MESSAGES group in the Diagnostic Transducer Block or in
FieldCare. See also Section 12.2 "Response of outputs to errors".
Every message is also output as per the FOUNDATION Fieldbus Specification by means of the
Transducer Error/XD_ERROR and Block Error/BLOCK_ERROR parameters in the Pressure,
Service and DP Flow Transducer Block. Numbers are given for these parameters in the following
table which are explained ä 218.
!
Note!
If the device detects a defect in the local operation during initialization, special error messages are
generated. For the error messages, ä 218, Section 12.1.1 "Local operation error
messages".
For support and further information, please contact Endress+Hauser Service.
Code Error
type/
NA 64
Message/description XD_
ERROR
Value
BLOCK_
ERROR
Bit
Cause Measure Prio-
rity
101 (A101) Alarm
B
B>Sensor electronic
EEPROM error
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI00382P (Deltabar S),
TI00383P (Cerabar S) or
TI00416P (Deltapilot S). This
message normally only appears
briefly.
Wait a few minutes.
Restart the device. Perform reset
(Code 62).
Block off electromagnetic effects
or eliminate source of
disturbance.
18
Sensor defect. Replace sensor.
102 (W102) Warning
C
C>Checksum error in
EEPROM: peakhold
segment
23 11 Main electronics defect. Correct
measurement can continue as
long as you do not need the
peak hold indicator function.
Replace main electronics. 52
106 (W106) Warning
C
C>Downloading - please
wait
17 0 Downloading. Wait for download to complete. 51
110 (A110) Alarm
B
B>Checksum error in
EEPROM: configuration
segment
23 11 The supply voltage is
disconnected when writing.
Reestablish supply voltage.
Perform reset if necessary
(code 7864) and recalibrate the
device.
6
Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI00382P (Deltabar S),
TI00383P (Cerabar S) or
TI00416P (Deltapilot S).
Block off electromagnetic effects
or eliminate sources of
disturbance.
Main electronics defect. Replace main electronics.
113 (A113) Alarm
B
B>ROM failure in
transmitter electronic
20 9 Main electronics defect. Replace main electronics. 1
115 (E115) Error
C
C>Sensor overpressure 17 0 Overpressure present. Reduce pressure until message
disappears.
30
Sensor defect. Replace sensor.