Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
62 Endress+Hauser
Comb. Measurand/
COMBINED_
MEASURAND
Selection
Index: 48
Data type: Unsigned
Access: OOS
Select the measured variable.
Options:
• Height and volume
• Height and mass
• Height and %
• %-height and volume
• %-height and mass
• %-height and %
!
Note!
This parameter can only be changed if the setting for the Linearization/LINEARIZATION
parameter (→ ä 57) suits it, e.g. if the "Flow square root" option was selected for the
Linearization/LINEARIZATION parameter, this parameter cannot be changed.
Factory setting:
%-height and %
Density Unit/
DENSITY_UNIT
Selection
Index: 49
Data type: unsigned16
Access: auto, OOS
Select the density unit.
Prerequisite:
• Comb. Measurand/COMBINED_MEASURAND = %-height and %,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = %-height and volume,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = %-height and mass,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = Height and %,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = Height and volume,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = Height and mass,
Calibration Mode/CALIBRATION_MODE = Dry
– Comb. Measurand = COMBINED_MEASURAND
– Calibration Mode = CALIBRATION_MODE
Options:
•g/cm
3
•kg/dm
3
•kg/m
3
• US lb/in
3
• US lb/ft
3
Factory setting:
kg/dm
3
Height Unit/
HEIGHT_UNIT
Selection
Index: 50
Data type: unsigned16
Access: auto, OOS
Select the level unit.
Prerequisite:
• Comb. Measurand/COMBINED_MEASURAND = Height and volume, height and mass or
height and %
Options:
•mm
•dm
•cm
•m
•inch
•ft
•User unit, → see also Customer Unit H/CUSTOMER_HEIGHT_UNIT (→ ä 63) and
Cust. Unit Fact. H/CUSTOMER_UNIT_FACTOR_HEIGHT (→ ä 63)
Factory setting:
m