Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 83
Unit Flow/
STD_FLOW_UNIT
Entry
Index: 16
Data type: UNSIGNED16
Access: read, write, OOS
Select flow unit.
Prerequisite:
• Deltabar S differential pressure transmitter
!
Note!
Make sure that the unit suits the flow mode selected. → ä 82, parameter description for
Flow-Meas. Type/FLOW_MEAS_TYPE.
When a new flow unit is selected, all flow-specific parameters are converted and displayed
with the new unit within a flow mode (Flow-Meas. Type/FLOW_MEAS_TYPE). When the
flow mode is changed, conversion is not possible.
Possible units for Flow-Meas. Type/FLOW_MEAS_TYPE = Volume operat. cond.:
• m3/s, m3/min, m3/h, m3/day
• l/s, l/min, l/h
• hl/s, hl/min, hl/day
• ft3/s, ft3/min, ft3/h, ft3/day
• ACFS, ACFM, ACFH, ACFD
•ozf/s, ozf/min
• US Gal/S, US Gal/min, US Gal/h, US Gal/day
• Imp. Gal/s, Imp. Gal/min, Imp. Gal/h
• bbl/s, bbl/min, bbl/h, bbl/day
• User unit, see also parameter description for Customer Unit F/CUSTOMER_UNIT_
FLOW (→ ä 84) and Cust. Unit Fact. F/CUSTOMER_UNIT_FACTOR_FLOW (→ ä 84)
Factory setting:
m³/s
Possible units for Flow-Meas. Type/FLOW_MEAS_TYPE = Volume norm. cond.:
• NM3/s, Nm3/min, Nm3/h, Nm3/day
•User unit,
→ see also parameter description for Customer Unit F/CUSTOMER_UNIT_
FLOW (→ ä 84) and Cust. Unit Fact. F/CUSTOMER_UNIT_FACTOR_FLOW (→ ä 84)
Factory setting:
Nm³/s
Possible units for Flow-Meas. Type/FLOW_MEAS_TYPE = Volume std. cond.:
• Sm3/s, Sm3/min, Sm3/h, Sm3/day
• SCFS, SCFM, SCFH, SCFD
•User unit,
→ see also parameter description for Customer Unit F/CUSTOMER_UNIT_
FLOW (→ ä 84) and FCust. Unit Fact. F/CUSTOMER_UNIT_FACTOR_FLOW
(→ ä 84)
Factory setting:
Sm3/s
Possible units for Flow-Meas. Type/FLOW_MEAS_TYPE = Mass p. cond.:
• g/s, kg/s, kg/min, kg/h
• t/s, t/min, t/h, t/day
•oz/s, oz/min
• lb/s, lb/min, lb/h
• ton/s, ton/min, ton/h, ton/day
•User unit,
→ see also parameter description for Customer Unit F/CUSTOMER_UNIT_
FLOW (→ ä 84) and Cust. Unit Fact. F/CUSTOMER_UNIT_FACTOR_FLOW (→ ä 84)
Factory setting:
kg/s
DP Flow Transducer Block
Parameter Description