44
Endress+Hauser
HART Loop Converter HMX50
4.2 Fault Message
The following table shows which fault message the current outputs send to the controller,
based on the characteristic.
5 Technical Specifications
5.1 Default Settings
The following table provides an overview of the default settings. Information about reset-
ting the device to the default setting see chapter 3.4.9.
If the device parameters have changed, enter these changes in the "Custom Value" column.
This provides an overview of your individual device settings.
Setting 4 - 20 unlimited 4 - 20 NE43
down
0 mA
Cannot be distinguished from falling
below the start value
2.0 mA
up
approx 23 mA
Cannot be distinguished from the end
value being exceeded
21.5 mA
hold Last measured value before the fault
BA00371FEN_1417.fm Page 44 Tuesday, August 15, 2017 4:08 PM