Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 183
Level unit
Navigation  Setup → Advanced setup → Interface → Level unit
Description Select level unit.
Selection SI units
%
m
mm
US units
ft
in
Factory setting %
Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→  159):
The unit defined in the Distance unit parameter is used for the basic calibration (Empty
calibration (→  161) and Full calibration (→  162)).
The unit defined in the Level unit parameter is used to display the (unlinearized) level
and interface position.
Blocking distance
Navigation  Setup → Advanced setup → Interface → Blocking dist.
Description Specify upper blocking distance UB.
User entry 0 to 200 m
Factory setting For coax probes: 100 mm (3.9 in)
For rod and rope probes up to 8 m (26 ft): 200 mm (8 in)
For rod and rope probes above 8 m (26 ft): 0.025 * length of probe
Additional information Echoes from within the blocking distance are not taken into account in the signal
evaluation. The upper blocking distance is used
to suppress interference echoes at the top end of the probe.
to suppress the echo of the total level in the case of flooded bypasses.