Electrical connection Levelflex FMP56, FMP57 FOUNDATION Fieldbus
36 Endress+Hauser
7.2.2 Connecting
A0036418
9 Dimensions: mm (in)
1. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
2. Remove the cable sheath.
3. Strip the cable ends over a length of 10 mm (0.4 in). In the case of stranded cables, also
fit ferrules.
4. Firmly tighten the cable glands.
5. Connect the cable in accordance with the terminal assignment.
A0034682
6. If using shielded cables: Connect the cable shield to the ground terminal.