Integration into a FOUNDATION Fieldbus network Levelflex FMP56, FMP57 FOUNDATION Fieldbus
38 Endress+Hauser
2. Turning securing clamp 90 ° counterclockwise and tighten the clamp with
2.5 Nm (1.84 lbf ft) again using the Allen key (3 mm).
7.3 Post-connection check
Is the device or cable undamaged (visual check)?
Do the cables comply with the requirements ?
Do the cables have adequate strain relief?
Are all cable glands installed, securely tightened and leak-tight?
Does the supply voltage match the specifications on the nameplate?
Is the terminal assignment correct?
If required: Has protective ground connection been established ?
If supply voltage is present, is the device ready for operation and do values appear on the display
module?
Are all housing covers installed and securely tightened?
Is the securing clamp tightened correctly?
8 Integration into a FOUNDATION Fieldbus network
8.1 Device Description (DD)
You require the following to configure a device and integrate it into an FF network:
• An FF configuration program
• The Cff file (Common File Format: *.cff)
• The device description (DD) in one of the following formats
– Device Description format 4 : *sym, *ffo
– Device Description format 5 : *sy5, *ff5
Information on the device-specific DD
Manufacturer ID 452B48hex
Device Type 100Fhex
Device Revision 05hex
DD Revision Information and files at:
• www.endress.com
• www.fieldcommgroup.org
CFF Revision