Commissioning (via operating menu) Levelflex FMP56, FMP57 FOUNDATION Fieldbus
50 Endress+Hauser
10.5 Configuration of a level measurement
A0012838
15 Configuration parameters for level measurements in solids
LN = Length of probe R = Reference point of the measurement
D = Distance E = Empty calibration (= Zero point)
L = Level F = Full calibration (= span)
1. Setup → Device tag
Enter tag for measuring point.
2. Setup → Distance unit
Select distance unit.
3. Setup → Bin type
Select bin property.
4. Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
5. Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
6. Setup → Level
Displays the measured level L.