EasyManua.ls Logo

Endress+Hauser Levelflex FMP56 - Configuration of a Level Measurement

Endress+Hauser Levelflex FMP56
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP56, FMP57 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 55
11.4 Configuration of a level measurement
The Setup method can also be used to configure the measurement. It is called up via the
SETUP (TRDSUP) transducer block.
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
A0012838
 17 Configuration parameters for level measurements in solids
LN = Length of probe R = Reference point of the measurement
D = Distance E = Empty calibration (= Zero point)
L = Level F = Full calibration (= span)
If for rope probes the DC value is less than 7, then measurement is not possible in the
area of the straining weight. In these cases, the maximum allowed value for the empty
calibration E is LN - 250 mm (LN - 10 in).

Other manuals for Endress+Hauser Levelflex FMP56

Related product manuals