Commissioning (block-based operation) Levelflex FMP56, FMP57 FOUNDATION Fieldbus
56 Endress+Hauser
Step Block Parameter Action
1 SETUP (TRDSUP) Distance unit
(distance_unit)
Select distance unit.
Selection:
1010: m
1013: mm
1018: in
1019: ft
2 SETUP (TRDSUP) Bin type (bin_type) Select bin type.
Selection:
33288: Metallic
33440: Plastic wood
33465: Concrete
33467: Aluminium
3 SETUP (TRDSUP) Empty calibration
(empty_calibration)
Enter the distance E between the reference point R
and the minimum level (0%).
4 SETUP (TRDSUP) Full calibration
(full_calibration)
Enter distance F between the minimum (0%) and
maximum (100%) level.
5 SETUP (TRDSUP) Level (level) Displays the measured level L.
6 SETUP (TRDSUP) Distance
(filtered_dist_val)
Displays the distance D between the reference
point R and the level L.
7 SETUP (TRDSUP) Signal quality
(signal_quality)
Displays the signal quality of the level echo.
8 SETUP (TRDSUP) Confirm distance
(confirm_distance)
Compare the displayed distance to the real distance
in order to start the recording of the mapping
curve.
Selection:
179: Manual map
32847: Delete all
32859: Distance ok
32860: Distance too big
32861: Distance too small
32862: Distance unknown
33100: Tank empty
11.5 Configuration of the on-site display
11.5.1 Factory settings of the on-site display for level measurements
Parameter Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Format display 1 value, max. size 1 value, max. size
Value 1 display Levele linearized Levele linearized
Value 2 display Distance Distance